Explore Mitsubishi Electric Products

255163-NF250-UV 4P 200A

255163 - NF250-UV 4P 200A

Material number 255163

Circuit breaker 4pole. In = 200A; Icu = Ics = 200kA at AC 440V

FA-MCCB: MOULDED-CASE CIRCUIT BREAKER
Series WS-V SERIES - MCCB
Type NF-U (ULTRA CURRENT-LIMITING)
Frame Size 250
Rated Current (A) 200
Current Type AC
Number of Poles 4
Rated Voltage (V) 690
Breaking Capacity at 400V (kA) 200/200
Compliant with Standard(s) IEC 60947-2, EN 60947-2
Cycles with Rated Current 10000
Cycles without Rated Current 25000
Automatic Tripping Device THERMAL-MAGNETIC
PRODUCT DIMENSIONS & WEIGHT
Depth (mm) 92
Weight (kg) 3,7
Width (mm) 140
Height (mm) 240
CONFORMITY
CE COMPLIANT
Shipping Approvals LR, DNV·GL, BV, ABS, CCS
UL/cUL NON-COMPLIANT
ENVIRONMENTAL
Dangerous Goods Class NO
WEEE B2B
Dangerous Goods Identifier NO