Explore Mitsubishi Electric Products
FR-F846-00083-E2-60L2-S6
Material number 577426
Delivering 3.7 kW at up to 7.6 A, the Mitsubishi Electric FR-F846-00083-E2-60L2-S6 is an IP55 FR-F800 inverter with main switch for three-phase 380–500 V. It suits air handling unit fans, chilled water pumps and water treatment pumps, with the switch giving local isolation at the drive. Control modes include V/F, advanced magnetic flux vector, optimum excitation and IPM motor control. An EMC filter, DC reactor and common mode choke are all built in, along with Safe Torque Off and an E2 Ethernet port. This compact frame has no cooling fan. The enclosure is IP55 for indoor installation at -10 to +40 °C, and a PLC function is included. Please contact DahebTech to confirm the details of this variant.
FA-INVERTER: INVERTER
| Series | FR-F800 SERIES |
|---|---|
| Type | FR-F846-E2-S6 WITH MAIN SWITCH |
| Minimum Rated Voltage (V) | 380 |
| Min. Permissible Voltage (V) | 323 |
| Maximum Rated Voltage (V) | 500 |
| Max. Permissible Voltage (V) | 550 |
| Current Type | AC |
| Phases | 3 |
| Rated Output Current LD (A) | 7,6 |
| Rated Motor Capacity LD (kW) | 3,7 |
| Frequency Range (Hz) | 0,2–590 |
| Control Method | V/F CONTROL, SOFT-PWM/HIGH FREQUENCY PWM, PM SENSORLESS VECTOR CONTROL, MAGNETIC FLUX VECTOR CONTROL |
| Motor Type | INDUCTION MOTOR, PM MOTOR |
| Integrated EMC Filter | YES |
| Safe Torque Off (STO) | YES |
| Regenerative (4Q) | NO |
| Integrated DC Choke | YES |
| Display | FR-DU08 |
| Display Type | 5 DIGITS LED (12 SEGMENT) |
| PLC Function | YES |
| Program Memory | 6K |
| Program Memory Unit | STEPS |
| Integrated Digital Inputs | 12 |
| Digital Outputs (Transistor) | 5 |
| Digital Outputs (Relay) | 2 |
| Integrated Analogue Inputs | 3 |
| Integrated Analogue Outputs | 2 |
| IO Type of Terminal Block | SPRING CLAMP |
| Expandable | YES |
| USB | 1+1 MINI |
| Ethernet Port | 1 |
| Built-In Network | iQSS, SLMP, MODBUS/TCP, MELSOFT/FA, CC-LINK IE FIELD NETWORK BASIC, BACNET/IP |
| Leakage Current (mA) | 2 |
| Power Loss SLD (W) | 130 |
| Standby Power Consumption (W) | 19 |
| Protection Class | IP55 |
PRODUCT DIMENSIONS & WEIGHT
| Depth (mm) | 325 |
|---|---|
| Weight (kg) | 15 |
| Width (mm) | 238 |
| Height (mm) | 520 |
CONFORMITY
| CE | COMPLIANT |
|---|---|
| Shipping Approvals | DNV,ABS |
| EAC | NON-COMPLIANT |
| UL/cUL | COMPLIANT |
| UKCA | COMPLIANT |
PRODUCT PACKAGING
| Aluminum (g) | 0 |
|---|---|
| Others (g) | 0 |
| Styrofoam (g) | 0 |
| Cardboard (g) | 3300 |
| Steel (g) | 0 |
| Glass (g) | 0 |
| Other plastic (g) | 50 |
| Wood (g) | 0 |
| Other paper (g) | 0 |
ENVIRONMENTAL
| REACH Limit Exceeded | YES |
|---|---|
| REACH Substance CAS Number | 119-47-1, 12626-81-2, 1317-36-8, 13560-89-9, 15571-58-1, 540-97-6, 541-02-6, 556-67-2, 68-12-2, 7439-92-1, 80-05-7, 96-45-7 |
| RoHS Compliance | COMPLIANT |
| Dangerous Goods Class | NO |
| WEEE | B2B |
| Dangerous Goods Identifier | NO |
Related Products
Frequently Asked Questions
3.7 kW at up to 7.6 A on three-phase 380–500 V, with a main switch.
An IP55 enclosure for indoor installation at -10 to +40 °C.
Air handling unit fans, chilled water pumps and water treatment pumps, with the switch giving local isolation. A PLC function is included.