Explore Mitsubishi Electric Products

288437-MMP-T32LF 13A

288437 - MMP-T32LF 13A

Material number 288437

Motor prot. switch. 5,5kW; Ir=9,0 ~ 13,0A; Icu AC 400V=15kA

FA-MMS: MANUAL MOTOR STARTER
Series MMP-T SERIES
Type MOTOR CIRCUIT BREAKERS
Compliant with Standard(s) EN 60947-4-1, EN 60947-2, IEC 60947-4-1, GB14048.2, IEC 60947-2
Frame Size 32
Number of Poles 3
Rated Current (A) 13
Rated Voltage (V) 690
Frequency Range (Hz) 50/60
Rated Capacity (kW) 5,5
Heater Designation (A) 13
Range of Setting Current (A) 9-13
Breaking Capacity at 415V (kA) ICU: 15; ICS: 7,5
Electrical Durability (Load) 100000 OPERATIONS
Mech. Durability (at no Load) 100000 OPERATIONS
Wiring SCREW-CLAMP
Automatic Tripping Device THERMAL-MAGNETIC (ADJUSTABLE)
PRODUCT DIMENSIONS & WEIGHT
Depth (mm) 82
Weight (kg) 0,33
Width (mm) 45
Height (mm) 90
CONFORMITY
CE COMPLIANT
EAC NON-COMPLIANT
UL/cUL NON-COMPLIANT
UKCA COMPLIANT
PRODUCT PACKAGING
Aluminum (g) 0
Others (g) 0
Styrofoam (g) 0
Cardboard (g) 0
Steel (g) 0
Glass (g) 0
Other plastic (g) 0
Wood (g) 0
Other paper (g) 53
ENVIRONMENTAL
REACH Limit Exceeded NO
RoHS Compliance COMPLIANT
Dangerous Goods Class NO
WEEE B2B
Dangerous Goods Identifier NO